400KVA 3 Phase Pure Sine Wave Inverter

AGP-400KVA

Specification

  • PHASE: 3 Phase lnput / 3 Phase Output
  • KVA: 400
  • INPUT(RECTIFIER)
  • Input Voltage: 190V/208V/380V/400V/415V/440V/480V/600V,3P4W or 3P3W
  • Input Range: +/-20%(>+/-20% is available upon request)
  • Input Frequency: 50/60Hz+/-5Hz
  • Power Walk In: 0% -100%:20 sec
  • Effciency: >98%
  • Voltage Regulation: +/-1%
  • BATTERY
  • Battery Type/Pcs: Maintenance free lead acid batteries/12V×29pcs
  • Maximum Charge Current Adc(Selectable): 160
  • Battery Start: Yes,UPS can be started without AC source
  • INVERTER
  • Output Voltage: 190V/208V/380V/400V/415V/440V/480V/600V,3P4W or 3P3W +/-1%
  • Wave Form: Sine Wave
  • Output Power Factor: 0.8
  • Frequency Lock Range: 50/60Hz+/-3Hz
  • Output Frequency(Free Running): 50/60Hz+/-0.1Hz
  • Phase Shift Under 100% Unbalance Load: <0.5°
  • THD(Linear Load): <2%
  • Overload <110%: Continuous
  • 110-125%: 15 minutes
  • 125-150%: 10 minutes
  • Efficiency(100%Load): 95%
  • STATIC SWITCH
  • Voltage Range: 173-277 VAC(L-N)
  • Mains ⇔Inverter: 0ms
  • OVERALL CHARACTERISTICS
  • Overall Efficiency: 93%
  • Maximum Heat Dissipation (Kw ): 17.4
  • Width x Height x Depth (mm): 2200x1600x800
  • Weight (Kg,Without battery): 2950
  • Audible Noise: <70 dBA ( At 1 M )
  • Temperature / Humidity: 0-40 °C; 32-104 ° F; 0%-90%(Non-Condensing)
  • Altitude:<1500 M Above Sea Level
  • FCC CLASS A,EN50091-1, -2: YES
  • Short Circuit Protection: YES
  • Lightning/EMC Filter: MOV/Input & Output
  • Galvanic Isolation: Input & Output true Galvanic Isolation
  • Indicator & Alarm: LCD, LED, Mimic, Display, Buzzer
  • Remote Control/Communication Inyerface: Monitoring 1~ 99 UPS simultaneously / Dry contact, RS232, RS485



Consult & Design by Ready-Market